Start-up synchro gensets - quick AMF without standard gen-set synchronization
Description:
- Aplication for faster start-up sequence of multiple generators.
- No need to synchronize generators and wait until all of them are synchronized on the same bus.
- Suitable for standby applications.
- Eliminates possible blackout time.
- Ideal for systems running on UPS.
- System available at full capacity in 8-10 seconds from start command.
- Start-up time remains constant even if the number of generators is increased to 10, 20 or 32.
- To avoid delaying availability of the system due to slow-starting generators or other problems, any engines that fail to reach running speed within a specified time are “rejected” from the scheme and, if able, are left to perform traditional synchronizing after the majority of sets have become available
- Traditional synchronizing available to allow for slow-starting generators.
- Automatic switching to traditional synchronizing in case insufficient sets are available to meet load’s requirements.
- Soft magnetizing of feed transformers – solves the problem where grid supply is not capable of supplying the inrush and decreases the overall cost of the installation.
Controllers options:
- 1x InteliSys NTC BaseBox (or InteliSys NT)
with IGS-NT-SUS software - 1x InteliGen NTC BaseBox (or InteliGen NT BaseBox or InteliGen NT or InteliGen NTC)
with IGS-NT-SUS software
Dongle options:
- IGS-NT-SUS-LSM+PMS dongle or IGS-NT-LSM+PMS dongle (for MINT, COX and COMBI archive only)
Related files:
- Software: IGS-NT-SUS 1.3
- Manuals: IGS-NT-SUS 1.3 New Features